Rodun International's thermal oil products are of the highest quality available. On this page, you will find all information about our thermal oil, associated systems, analyses, equipment, and
In this article, you will find all the thermal oil information you need. For example, you can read more about
- Thermal oil properties: what do you need to know?
- What do we mean by heat-transferring oil?
- Heat transfer fluids: what does that entail?
- What does the heat transfer process look like?
- Thermal oil systems and the development of an expansion vessel: everything you need to know
- Flushing a thermal system
- HTF Systems and Expansion Vessels: What You Need to Know
- Thermal oil information, old oil, filtration, and taking dirt and oil samples
- Where you can find our MSDS Sheets
- More about Rodun and our Thermal oil
- How do I contact Rodun regarding my questions about thermal oil?
Thermal oil properties: what do you need to know?
Once the right product for your application has been selected, you can be assured that the product will give the installation a very long service life, provided the installation operates under the correct conditions. Regular analysis of oil samples will provide you with the current condition of the fluid. If corrective measures are necessary, this will become apparent from the analysis to extend the service life and safety of the installation. Would you like to read more about the properties of thermal oil? Then read our blog 'Thermal oil properties' and find out:
- What the best medium for heat transfer is
- What the effects of cold and higher temperatures are
- What synthetic thermal oils consist of
- Which products are available at Rodun International BV Rodun International's thermal oil products are of the highest quality available. On this page, you will find all information about our thermal oil, associated systems, analyses, equipment, and
In this article, you will find all the thermal oil information you need. For example, you can read more about
- Thermal oil properties: what do you need to know?
- What do we mean by heat-transferring oil?
- Heat transfer fluids: what does that entail?
- What does the heat transfer process look like?
- Thermal oil systems and the development of an expansion vessel: everything you need to know
- Flushing a thermal system
- HTF Systems and Expansion Vessels: What You Need to Know
- Thermal oil information, old oil, filtration, and taking dirt and oil samples
- Where you can find our MSDS Sheets
- More about Rodun and our Thermal oil
- How do I contact Rodun regarding my questions about thermal oil?
Thermal oil properties: what do you need to know?
Once the right product for your application has been selected, you can be assured that the product will give the installation a very long service life, provided the installation operates under the correct conditions. Regular analysis of oil samples will provide you with the current condition of the fluid. If corrective measures are necessary, this will become apparent from the analysis to extend the service life and safety of the installation. Would you like to read more about the properties of thermal oil? Then read our blog 'Thermal oil properties' and find out:
- What the best medium for heat transfer is
- What the effects of cold and higher temperatures are
- What synthetic thermal oils consist of
- Which products are available at Rodun International BV
Heat-transferring oil: what exactly do we mean by that?
What exactly do we mean by heat-transferring oil? And what requirements are placed on thermal fluids or thermal oil? Please also note that you can view our product page. There are various selection options to ensure you make the right choice.
Heat transfer fluids: what does that entail?
On the 'Heat-transferring fluids' page, you will learn what you need to know about why it is a broader concept than just heat-transferring oil.
What exactly does the heat transfer process look like?
High-quality process heat transfer is extremely important for virtually all process-related industrial enterprises. These are typically companies that operate continuously and require a large to very large amount of heat 365 days a year to supply the processes with the necessary heat. You can find some examples of this on the 'Process heat transfer' page.
Thermal oil, thermal systems, and the development of an expansion tank: everything you need to know
The design of an expansion tank for a thermal system operating in the liquid phase is a very important factor for the successful operation of that system. A correctly installed and maintained expansion tank contributes to extending the lifespan of the oil and lowering maintenance costs. A well-designed expansion tank can prevent many problems, especially during the start-up and daily use of the system. In the following discussion, you will discover the purpose and design of an expansion tank. You should always consult a qualified engineering firm when a new thermal system or part thereof is being considered, especially since some parts of the system can be critical to its proper functioning. If desired, we can always advise you and assist you in ultimately achieving an excellent 'engineered system'. Also read our blog 'Thermal Oil Systems'.
Flushing a thermal system
In severely contaminated thermal systems, often caused by the use of an incorrect thermal fluid, heat transfer efficiency is no longer at the desired level and the safety of such an installation can be seriously compromised. Instrumentation lines in particular can become clogged, with all the associated consequences. Read more about this on the page 'Flushing a thermal system'.
HTF systems expansion vessels: the purpose and what you need to know
As stated above, the primary purpose of an expansion tank in a thermal system is to allow the oil to expand, even if this can exceed 25% of the volume, depending on the type of oil and the operating temperature. Because the tank is usually installed at the highest point of the system, it can also function as a vent for the low-boiling components of the liquid and the moisture that may build up in the HTF fluid. The high placement also creates good pressure at the pump inlet side, ensuring a continuous supply of liquid to the secondary circuit.
Please also read our 'HTF System' page on this topic.
Figure 1 shows a simple design of an expansion tank for a thermal system.
Figure 1: Schematic diagram of an expansion tank for a thermal system.Design parameters for an expansion tank
There are various basic design parameters for every HTF system expansion tank that can provide optimal benefit from the tank, and thereby ensure optimal operation.
What are the dimensions of the tank?
The tank dimensions must be calculated such that the tank is 25% full at ambient temperature and 75% full at operating temperature. The dimensions should have a favorable influence on the liquid pressure towards the pump suction side during startup, and you should keep the vapor space in the tank as small as possible during normal operation. Liquid expansion between two temperatures can be calculated by dividing the liquid density at the lower temperature by the liquid density at the higher temperature.
Double downpipes and valves
The expansion tank must be positioned at the highest part of the system, with a double piping system, as shown in Figure 2. If the sole purpose of the tank were to accommodate expansion, a single piping system would suffice; however, the tank also provides the best point for venting the ducts. To ensure a good venting function of the expansion vessel, maximum system flow must be possible. The pipes to and from the expansion tank must be able to handle the full fluid flow during startup conditions. Under normal operating conditions, valves A and C are open and B, D, E, and F are closed. To admit fluid after startup, valve D must be used. The initial filling of the system should be done by opening valve E together with valves B, C, and F. This is the most efficient way to force air out of the system. The expansion vessel should be the primary point in the system for removing moisture and ducts. New systems almost always contain a quantity of moisture that enters the system during construction and atmospheric condensation. This moisture must be removed during the startup procedure to prevent cavitation. To utilize the expansion tank as a 'vent', valves A, D, and E must be closed, while valves B, C, and F must remain open. The system temperature must be slowly raised from 150°C to 180°C. As soon as you observe that all layer boilers have boiled out (steam plume has disappeared), valve A must be opened and valves B and F closed. As soon as the volume of layer boilers increases, this procedure must be repeated; however, in this case, the expansion tank must reach the system temperature before valve A is opened.
Figure 2: Nitrogen installation on an expansion tank.Instrumentation
It is essential that proper instrumentation is arranged in the design of the expansion tank and other components of the HTF system. The expansion tank must be equipped with both maximum and minimum level alarms, combined with a low-level switch that automatically shuts off the boiler and pump in the event of thermal fluid leakage. Pressure relief valves must be present in the expansion tank design with the capability to drain excess fluid to an area where it will not inconvenience personnel or pose a fire hazard. A high-temperature sight glass must be installed as a visual aid on the level sensors.
Nitrogen blanket on the expansion tank
All types of organic thermal oils, including our fluids, undergo oxidation when exposed to oxygen, i.e., air. This oxidation process causes a significant amount of solid dirt particles and deposits in the system, negatively affecting heat transfer and potentially damaging the gaskets. The extent of the contamination depends on the amount of oxygen coming into contact with the fluid and, naturally, the temperature. The usual source of contact with oxygen is in the expansion vessel. An effective method to prevent this fluid oxidation is achieved by covering the fluid with a nitrogen blanket. Usually, nitrogen, CO2, or natural gas is used for this purpose. Figure 2 shows a suggested solution for a so-called 'Blanketing' system on the expansion vessel. The ultimate goal of such a gas seal is to maintain a non-reactive atmosphere with the thermal fluid in the expansion tank, thereby preventing the ingress of moisture and air that negatively affect the lifespan of the thermal oil. A continuous flow, usually nitrogen, on both sides of the expansion vessel, controlled by pressure regulating valves, is necessary to regulate the flow. A pressure relief valve is also necessary to protect the tank against overpressure in the event that the pressure regulating valves fail, in the event of a fire, or for other reasons. The nitrogen pressure should be kept as low as possible to keep nitrogen consumption low. Maintaining a positive pressure just slightly higher than atmospheric pressure is sufficient to prevent the entry of air and moisture into the tank. A manually operated vent valve must also be installed to allow for the venting of the HTF fluid low boilers and any moisture, also known as boiling out.
Figure 3: Condensate collection system on an expansion tank.Condensate collection method
Covering the expansion tank with a nitrogen blanket is the most common way to prevent liquid oxidation. If this method is not possible, there is an alternative, though not as reliable, that utilizes condensate collection. Figure 3 shows a typical condensate collection system on an expansion tank. In English, this is called a 'cold seal trap'. The drawback of this type of system is that the amount of liquid supplied between the main system and the condensate tank during boiling is difficult to regulate. You must ensure that this effect is minimized by using a very carefully calculated size for the condensate tank and the drain pipe.
Thermal oil information, old oil, filtration, taking dirt and oil samples
Have you purchased new HTF from us, or are you planning a change and suddenly thinking, “what am I going to do with my old oil”? Well, that is very simple. You can read about it on the page 'What should I do with my old oil?'
Thermal oil filtration: how and why?
Indirect heating of processes using organic thermal oil, such as Eastman's thermal heat transfer fluids, offers a high degree of reliability. HTF systems in general are considered low-maintenance systems. In certain cases, an HTF system may become contaminated with sludge particles, or other sources of dirt may enter the system. This contamination can be the cause of operational problems. The hard particles can cause gasket problems on the shafts of circulation pumps, valve wear, clogging, and even fouling on the heat exchanger. In many cases, these problems can be resolved by using a filter. For severely contaminated systems, more intensive cleaning is required. In some cases, the oil can be filtered externally. Filtration can help prevent dirt from entering the system during startup.
What does the dirt consist of?
The contamination can consist of diverse types, such as dirt created during system build-up, mill scale, and reaction products of the HTF oil with oxidizing substances, namely air, acids, and process leaks into the HTF oil. Other forms of contamination, such as rust and metal oxides, are no exception. Some less stable HTF fluids automatically produce insoluble contamination when they exceed their maximum temperature limit.
Which filters are needed?
For 'in' system filtration, fiberglass spun filters can be used, which usually suffice. However, they must be able to withstand temperatures of 350-400°C. They have excellent dirt-holding capacity, are inexpensive, and easy to dispose of. Metal filters are generally more expensive but can be cleaned and reused quickly. There are many types of fiberglass filter elements that can be used, but they, like the filter housing, must withstand the required temperature. You should check for yourself whether local or national regulations exist for this type of product. In many cases, O-seals do not meet the requirements demanded at high temperatures and pressures. HTF oil usually dissolves standard seals, so special seals are required. Reinforced flexible graphite gaskets generally do suffice. You can, of course, also consult a Therminol advisor. Every filter housing and its components must meet the specified requirements for the operating temperature at which the filter is used.
Because there are so many different filter manufacturers, it is advisable, before deciding to make your choice, to ensure that your selection is substantiated by the manufacturer with a certificate or datasheet confirming the temperature and pressure limits, as well as resistance to thermal oil.Filter installation and use
For high-temperature applications, spun glass fiber filters can be installed where there is a pressure drop of 1.4 to 2.8 kg/cm² in the system. The maximum flow rate through the filter should not exceed 1% of the main flow velocity and should not exceed 18 liters/min at a filter length of 25 cm. At the desired flow rate, an initial pressure drop of 0.07 to 0.14 kg/cm² is desirable. Under these conditions, one or more system volumes of HTF oil should pass through the filter. To prevent excessive pressure drop and to assist the filter, a pressure relief valve should be set to 1.8 to 2.1 kg/cm². If a potential backflow occurs across the filter, a check valve must be installed to prevent filter failure. Flexible and reinforced graphite gaskets must always be used. In this type of system, it is common practice to weld pipes rather than flanges. The filter must be insulated exclusively with a non-absorbent insulating material. The filter must be placed where it can be easily maintained. During operation, the pressure drop and flow rate must be checked daily to determine whether the filter element needs to be replaced. Hard solid particles build up a layer on the filter, revealing a shiny, wet surface.
The filter element must be disposed of in an environmentally friendly manner.Size of the filter
The HTF fluid analysis program determines the particle size of insoluble dirt above 1 micron for used oil samples. The level of insoluble dirt is determined by laboratory filtration through a 1-micron membrane filter, in which the solid particles are washed by acetone or pentane. Particles larger than 1 micron are responsible for a large proportion of all problems in HTF systems. The solid particle measurement is expressed in ppm (parts per million). Assuming that the HTF oil and dirt have a density of 1 g/ml, 1 mg/100 ml is equal to 10 ppm.
Conventional filter elements can capture 40,000 to 100,000 mg of solid particles per 25 cm of filter length. While a 1-micron filter could be used, there is always the risk of filter or surface clogging. A better technique is to start with a coarser filter with, for example, 50 or 100 micron elements and gradually move to finer elements. The frequency of filter element replacement should be balanced with the size of the filter housing, which should be related to the total volume of the HTF system. Filter cleaning should be performed based on dirt data, particle size, filter element size, etc. After a complete filter cleanup, we always recommend permanently incorporating a 5 micron element into the filter housing to serve as a diagnostic tool for any future contamination.
Testing thermal oil
When thermal oil is used within the recommended temperature limits, the oil can last for years. To ensure a long service life for the thermal oil, we offer an oil testing service through Eastman Chemical. This service helps detect system faults, oil contamination, moisture, oxidation, and other causes that can adversely affect the thermal system.
What does our analysis program consist of?
Testing begins when an oil sample from a system put into operation is submitted for analysis. By far the majority of samples require routine analysis. In other cases, extensive analyses are performed to identify the cause of problems in the system. The oil can be tested for acidity, moisture, insoluble impurities, viscosity, high and low boilers, and other factors that may affect the system. Once the analysis has been performed, recommendations will be made to increase system efficiency and extend the lifespan of the oil. All of this is documented in a report. Our knowledge of the products, in comparison with the oil sample analysis and the established limits, provides indications for possible corrective measures to prevent further problems.
How often must a thermal system be checked?
Analysis is required for newly commissioned systems, systems that have been cleaned, or systems to which different oil has been added. Additionally, any system operating continuously at the oil's maximum temperature limits must be analyzed once a year. Once every three years is sufficient if the oil is used in the thermal system at temperatures 30 to 40°C below its maximum temperature limit. In the event of a problem, the analysis can immediately provide an indication of the cause and magnitude of the problem, as well as the urgency of necessary corrections.
How can I request an analysis?
Requests for chemical oil analysis can be made by telephone, +31(0)6 10 27 52 11 or via [email protected] Upon request, we will send you one or more sample bottles. You must complete the form contained in the cardboard tube and send it along with the oil sample to the indicated address.
How do I take a representative oil sample?
- Only the sets of sample bottles sent by us may be used. Other samples will not be analyzed. The set contains an aluminium bottle and a form.
- A full bottle is required for analysis. Take oil from the circulation section of the system; if possible, take a cold sample. If hot oil is drawn from the system as a sample, allow it to cool down while tightly sealed, then pour it into the aluminum bottle and seal it immediately.
- Drawing a hot sample can be life-threatening and must be performed exclusively by certified personnel equipped with the appropriate protective clothing and tools. If you do not have those people, we can take a hot sample for you.
- Ensure the oil sample is properly sealed and check that the bottle does not leak. Place the bottle in the cardboard container and enclose the completed form. Place the entire package in a padded envelope labeled with the address below and send it by courier or simply by post.
Send the oil sample to:
- Rodun International BV
- Productieweg 8
- 3481 MH Harmelen
- The Netherlands
How soon can you expect the analysis?
Under normal circumstances, you will receive the results within two to three weeks, possibly with advice for corrective measures. In the case of an urgent analysis, this can be done within 48 hours.
What do the test results actually mean?
Our experience with operational oil analyses enables us to determine the oil property limits. If all test results fall within the 'normal' range, the oil is in good condition, and reported system problems are usually design or operational issues. If one or more properties fall under a 'warning', the necessary corrective measures must be implemented to minimize further change to the oil or the system. Serious deviations require further investigation with more stringent corrective measures or oil replacement to ensure acceptable system operation.
Although the analysis reveals problems and recommends corrective measures, the customer can decide for themselves which measures they deem necessary and wish to implement.
Viscosity: Changes in viscosity indicate contamination, thermal stress, and/or oxidation. Viscosity is related to the molecular weight of the oil components. As a rule, contamination by foreign substances in the thermal oil, thermal stress, and oxidation are the causes of an increase or decrease in the oil's viscosity. The operation of the system can be adversely affected by viscosity deviations. If the viscosity is very high, start-up problems may occur, resulting in the burner shutting off. Heat transfer properties may also decrease. At low viscosity, the low-boiling components of the oil can cause cavitation of the pump(s), resulting in reduced flow.
To remove the low-boiling components, the oil must be routed through the expansion vessel to vent them.
High viscosity usually requires oil replacement; however, corrections can also be achieved with partial replacement. In all cases, the cause of the viscosity change must be investigated. Malfunctioning parts or incorrect oil can cause thermal degradation and oxidation. Repair and a better oil can improve the situation.
Acidity: Generally, a high acidity indicates contamination by substances that do not belong in the thermal oil. A high acidity can also arise from the absence of 'nitrogen blanketing' on the expansion vessel. If the acidity level becomes too high, corrosion occurs and problems may arise. Corrosive materials form sludge and deposits that negatively affect heat transfer. A severe oxidation situation often requires oil replacement.
Moisture: Moisture in the system usually indicates a leak on the process side or that moisture has otherwise entered the system. New systems, flushed with water, open tank valves, etc., can cause moisture in the system. Rust formation, high system pressure, pump cavitation, and vapor lock are usually indications of excessive moisture in the system. If hot oil comes into contact with an accumulation of water, a steam explosion can occur with all the associated consequences. Exceptionally careful start-up of the system with good circulation throughout the entire system is necessary until the water reaches above the boiling point. The heating oil must flow through the expansion tank, where the moisture can be boiled out. In the event of a very large amount of water, the oil must be removed from the system for an external drying process. Leaking system parts must always be repaired promptly, and new oil must be used to prevent water from entering the system.
Note: If vessels are stored outdoors, ensure they are well protected from the effects of rain.
Insoluble dirt: The presence of insoluble dirt generally indicates that the thermal load on the system is too high due to corrosion products and high oxidation. This causes deposits on the heat transfer surface, blockages, and wear on mechanical seals and valves. If this occurs, a bypass filter can often be a solution. If the amounts of dirt are extremely high, consideration should be given to having the fluid filtered externally and the system thoroughly cleaned. Therminol-FF has proven to be very effective in removing deposits from synthetic and mineral thermal oil systems. In cases of less contamination, a good filter with a fineness between 10 and 25 microns may suffice.
LOW- AND HIGH-BOILING COMPONENTS Low- and high-boiling materials are measured by gas chromatographic analysis and generally reveal fouling, oxidation, and thermal stress of the oil. This can cause pump cavitation, poor circulation, and reduced heat transfer. This can result in deposits on heat transfer surfaces and insoluble dirt.
To correct this, the low-boilers must be vented and the abnormal thermal stress corrected.
Extreme amounts of low- and/or high-boilers must be removed externally or the oil must be replaced.Can I test the oil in my own laboratory?
Rodun's test procedures are based on standard ASTM and/or DIN methods for the analysis of mineral and synthetic chemical fluids. Special analytical tests are not immediately necessary for a quick visual assessment of the oil's condition. Moisture causes a cloudy liquid or separation between moisture and oil.
The viscosity of new and used oil should be virtually identical. The color of used oil is usually dark brown. A significant amount of dirt is usually visible at the bottom of a laboratory tube.
In general, it can be stated that thorough laboratory analysis is necessary for a proper evaluation of the oil.MSDS Sheets Rodun International
Would you like to download our MSDS sheets? On this overview page, you will find all MSDS sheets from Rodun International. You can request the data directly in PDF format.
About Rodun International
Thermal oil is our company's specialty. For advice, chemical analyses, and the supply of all synthetic thermal fluids, thermal installations, and systems, you will find the right partner in Rodun International BV. Read more about us on our 'About Rodun International' page. Additionally, follow us on LinkedIn to always stay up to date.
Contact Rodun International
For advice, chemical analyses, and the supply of all synthetic thermal fluids, thermal installations, and systems, Rodun International BV is the right place for you. Contact us for more information or no-obligation advice.
Heat-transferring oil: what exactly do we mean by that?
What exactly do we mean by heat-transferring oil? And what requirements are placed on thermal fluids or thermal oil? Please also note that you can view our product page. There are various selection options to ensure you make the right choice.
Heat transfer fluids: what does that entail?
On the 'Heat-transferring fluids' page, you will learn what you need to know about why it is a broader concept than just heat-transferring oil.
What exactly does the heat transfer process look like?
High-quality process heat transfer is extremely important for virtually all process-related industrial enterprises. These are typically companies that operate continuously and require a large to very large amount of heat 365 days a year to supply the processes with the necessary heat. You can find some examples of this on the 'Process heat transfer' page.
Thermal oil, thermal systems, and the development of an expansion tank: everything you need to know
The design of an expansion tank for a thermal system operating in the liquid phase is a very important factor for the successful operation of that system. A correctly installed and maintained expansion tank contributes to extending the lifespan of the oil and lowering maintenance costs. A well-designed expansion tank can prevent many problems, especially during the start-up and daily use of the system. In the following discussion, you will discover the purpose and design of an expansion tank. You should always consult a qualified engineering firm when a new thermal system or part thereof is being considered, especially since some parts of the system can be critical to its proper functioning. If desired, we can always advise you and assist you in ultimately achieving an excellent 'engineered system'. Also read our blog 'Thermal Oil Systems'.
Flushing a thermal system
In severely contaminated thermal systems, often caused by the use of an incorrect thermal fluid, heat transfer efficiency is no longer at the desired level and the safety of such an installation can be seriously compromised. Instrumentation lines in particular can become clogged, with all the associated consequences. Read more about this on the page 'Flushing a thermal system'.
HTF systems expansion vessels: the purpose and what you need to know
As stated above, the primary purpose of an expansion tank in a thermal system is to allow the oil to expand, even if this can exceed 25% of the volume, depending on the type of oil and the operating temperature. Because the tank is usually installed at the highest point of the system, it can also function as a vent for the low-boiling components of the liquid and the moisture that may build up in the HTF fluid. The high placement also creates good pressure at the pump inlet side, ensuring a continuous supply of liquid to the secondary circuit.
Read our 'HTF System' page about this as well.
Figure 1 shows a simple design of an expansion tank for a thermal system.
Figure 1: The schematic diagram of an expansion tank for a thermal system.
Design parameters for an expansion tank
There are various basic design parameters for every HTF system expansion tank that can provide optimal benefit from the tank, and thereby ensure optimal operation.
What are the dimensions of the tank?
The tank dimensions must be calculated such that the tank is 25% full at ambient temperature and 75% full at operating temperature. The dimensions should have a favorable influence on the liquid pressure towards the pump suction side during startup, and you should keep the vapor space in the tank as small as possible during normal operation. Liquid expansion between two temperatures can be calculated by dividing the liquid density at the lower temperature by the liquid density at the higher temperature.
Double downpipes and valves
The expansion tank must be positioned at the highest part of the system, with a double piping system, as shown in Figure 2. If the sole purpose of the tank were to accommodate expansion, a single piping system would suffice; however, the tank also provides the best point for venting the ducts. To ensure a good venting function of the expansion vessel, maximum system flow must be possible. The pipes to and from the expansion tank must be able to handle the full fluid flow during startup conditions. Under normal operating conditions, valves A and C are open and B, D, E, and F are closed. To admit fluid after startup, valve D must be used. The initial filling of the system should be done by opening valve E together with valves B, C, and F. This is the most efficient way to force air out of the system. The expansion vessel should be the primary point in the system for removing moisture and ducts. New systems almost always contain a quantity of moisture that enters the system during construction and atmospheric condensation. This moisture must be removed during the startup procedure to prevent cavitation. To utilize the expansion tank as a 'vent', valves A, D, and E must be closed, while valves B, C, and F must remain open. The system temperature must be slowly raised from 150°C to 180°C. As soon as you observe that all layer boilers have boiled out (steam plume has disappeared), valve A must be opened and valves B and F closed. As soon as the amount of layer boilers increases, this procedure must be repeated; however, in this case, the expansion tank must reach the system temperature before valve A is opened.
Figure 2: Nitrogen installation on an expansion tank.
Instrumentation
It is essential that proper instrumentation is arranged in the design of the expansion tank and other components of the HTF system. The expansion tank must be equipped with both maximum and minimum level alarms, combined with a low-level switch that automatically shuts off the boiler and pump in the event of thermal fluid leakage. Pressure relief valves must be present in the expansion tank design with the capability to drain excess fluid to an area where it will not inconvenience personnel or pose a fire hazard. A high-temperature sight glass must be installed as a visual aid on the level sensors.
Nitrogen blanket on the expansion tank
All types of organic thermal oils, including our fluids, undergo oxidation when exposed to oxygen, i.e., air. This oxidation process causes a significant amount of solid dirt particles and deposits in the system, negatively affecting heat transfer and potentially damaging the gaskets. The extent of the contamination depends on the amount of oxygen coming into contact with the fluid and, naturally, the temperature. The usual source of contact with oxygen is in the expansion vessel. An effective method to prevent this fluid oxidation is achieved by covering the fluid with a nitrogen blanket. Usually, nitrogen, CO2, or natural gas is used for this purpose. Figure 2 shows a suggested solution for a so-called 'Blanketing' system on the expansion vessel. The ultimate goal of such a gas seal is to maintain a non-reactive atmosphere with the thermal fluid in the expansion tank, thereby preventing the ingress of moisture and air that negatively affect the lifespan of the thermal oil. A continuous flow, usually nitrogen, on both sides of the expansion vessel, controlled by pressure regulating valves, is necessary to regulate the flow. A pressure relief valve is also necessary to protect the tank against overpressure in the event that the pressure regulating valves fail, in the event of a fire, or for other reasons. The nitrogen pressure must be kept as low as possible to keep nitrogen consumption low. Maintaining a positive pressure just slightly higher than atmospheric pressure is sufficient to prevent the entry of air and moisture into the tank. A manually operated vent valve must also be installed to allow for the venting of the HTF fluid low boilers and any moisture, also known as boiling out.
Figure 3: Condensate collection system on an expansion tank
Condensate collection method
Covering the expansion tank with a nitrogen blanket is the most common way to prevent liquid oxidation. If this method is not possible, there is an alternative, though not as reliable, that utilizes condensate collection. Figure 3 shows a typical condensate collection system on an expansion tank. In English, this is called a 'cold seal trap'. The drawback of this type of system is that the amount of liquid supplied between the main system and the condensate tank during boiling is difficult to regulate. You must ensure that this effect is minimized by using a very carefully calculated size for the condensate tank and the drain pipe.
Thermal oil information, old oil, filtration, taking dirt and oil samples
Have you purchased new HTF from us, or are you planning a change and suddenly thinking, “what am I going to do with my old oil”? Well, that is very simple. You can read about it on the page 'What should I do with my old oil?'
Thermal oil filtration: how and why?
Indirect heating of processes using organic thermal oil, such as Eastman's thermal heat transfer fluids, offers a high degree of reliability. HTF systems in general are considered low-maintenance systems. In certain cases, an HTF system may become contaminated with sludge particles, or other sources of dirt may enter the system. This contamination can be the cause of operational problems. The hard particles can cause gasket problems on the shafts of circulation pumps, valve wear, clogging, and even fouling on the heat exchanger. In many cases, these problems can be resolved by using a filter. For severely contaminated systems, more intensive cleaning is required. In some cases, the oil can be filtered externally. Filtration can help prevent dirt from entering the system during startup.
What does the dirt consist of?
The contamination can consist of diverse types, such as dirt created during system build-up, mill scale, and reaction products of the HTF oil with oxidizing substances, namely air, acids, and process leaks into the HTF oil. Other forms of contamination, such as rust and metal oxides, are no exception. Some less stable HTF fluids automatically produce insoluble contamination when they exceed their maximum temperature limit.
Which filters are needed?
For 'in' system filtration, fiberglass spun filters can be used, which usually suffice. However, they must be able to withstand temperatures of 350-400°C. They have excellent dirt-holding capacity, are inexpensive, and easy to dispose of. Metal filters are generally more expensive but can be cleaned and reused quickly. There are many types of fiberglass filter elements that can be used, but they, like the filter housing, must withstand the required temperature. You should check for yourself whether local or national regulations exist for this type of product. In many cases, O-seals do not meet the requirements demanded at high temperatures and pressures. HTF oil usually dissolves standard seals, so special seals are required. Reinforced flexible graphite gaskets generally do suffice. You can, of course, also consult a Therminol advisor. Every filter housing and its components must meet the specified requirements for the operating temperature at which the filter is used.
Because there are so many different filter manufacturers, it is advisable, before deciding to make your choice, to ensure that your selection is substantiated by the manufacturer with a certificate or datasheet confirming the temperature and pressure limits, as well as resistance to thermal oil.
Filter installation and use
For high-temperature applications, spun glass fiber filters can be installed where there is a pressure drop of 1.4 to 2.8 kg/cm² in the system. The maximum flow rate through the filter should not exceed 1% of the main flow velocity and should not exceed 18 liters/min at a filter length of 25 cm. At the desired flow rate, an initial pressure drop of 0.07 to 0.14 kg/cm² is desirable. Under these conditions, one or more system volumes of HTF oil should pass through the filter. To prevent excessive pressure drop and to assist the filter, a pressure relief valve should be set to 1.8 to 2.1 kg/cm². If a potential backflow occurs across the filter, a check valve must be installed to prevent filter failure. Flexible and reinforced graphite gaskets must always be used. In this type of system, it is common practice to weld pipes rather than flanges. The filter must be insulated exclusively with a non-absorbent insulating material. The filter should be placed where it can be easily maintained. During operation, the pressure drop and flow rate must be checked daily to determine whether the filter element needs to be replaced. Hard solid particles build up a layer on the filter, revealing a shiny, wet surface.
The filter element must be disposed of in an environmentally friendly manner.
Size of the filter
The HTF fluid analysis program determines the particle size of insoluble dirt above 1 micron for used oil samples. The level of insoluble dirt is determined by laboratory filtration through a 1-micron membrane filter, in which the solid particles are washed with acetone or pentane. Particles larger than 1 micron are responsible for a large proportion of all problems in HTF systems. The solid particle measurement is expressed in ppm (parts per million). Assuming that the HTF oil and dirt have a density of 1 g/ml, 1 mg/100 ml is equal to 10 ppm.
Standard filter elements can capture 40,000 to 100,000 mg of solid particles per 25 cm of filter length. While a 1-micron filter could be used, there is always the risk of filter or surface clogging. A better technique is to start with a coarser filter, for example with 50 or 100-micron elements, and gradually progress to finer elements. The frequency of filter element replacement should be balanced with the size of the filter housing, which should be related to the total volume of the HTF system. Filter cleaning should be performed based on dirt levels, particle size, filter element size, etc. After a complete filter cleanup, we always recommend permanently incorporating a 5-micron element into the filter housing to serve as a diagnostic tool for any future contamination.
Testing thermal oil
When thermal oil is used within the recommended temperature limits, the oil can last for years. To ensure a long service life for the thermal oil, we offer an oil testing service through Eastman Chemical. This service helps detect system faults, oil contamination, moisture, oxidation, and other causes that can adversely affect the thermal system.
What does our analysis program consist of?
Testing begins when an oil sample from a system put into operation is submitted for analysis. By far the majority of samples require routine analysis. In other cases, extensive analyses are performed to identify the cause of problems in the system. The oil can be tested for acidity, moisture, insoluble impurities, viscosity, high and low boilers, and other factors that may affect the system. Once the analysis has been performed, recommendations will be made to increase system efficiency and extend the lifespan of the oil. All of this is documented in a report. Our knowledge of the products, in comparison with the oil sample analysis and the established limits, provides indications for possible corrective measures to prevent further problems.
How often must a thermal system be checked?
Analysis is required for newly commissioned systems, systems that have been cleaned, or systems to which different oil has been added. Additionally, any system operating continuously at the oil's maximum temperature limits must be analyzed once a year. Once every three years is sufficient if the oil is used in the thermal system at temperatures 30 to 40°C below its maximum temperature limit. In the event of a problem, the analysis can immediately provide an indication of the cause and magnitude of the problem, as well as the urgency of necessary corrections.
How can I request an analysis?
Requests for chemical oil analysis can be made by telephone, +31(0)6 10 27 52 11 or via [email protected] Upon request, we will send you one or more sample bottles. You must complete the form contained in the cardboard tube and send it along with the oil sample to the indicated address.
How do I take a representative oil sample?
- Only the sets of sample bottles sent by us may be used. Other samples will not be analyzed. The set contains an aluminium bottle and a form.
- A full bottle is required for analysis. Take oil from the circulation section of the system; if possible, take a cold sample. If hot oil is drawn from the system as a sample, allow it to cool down while tightly sealed, then pour it into the aluminum bottle and seal it immediately.
- Drawing a hot sample can be life-threatening and must be performed exclusively by certified personnel equipped with the appropriate protective clothing and tools. If you do not have those people, we can take a hot sample for you.
- Ensure the oil sample is properly sealed and check that the bottle does not leak. Place the bottle in the cardboard container and enclose the completed form. Place the entire package in a padded envelope labeled with the address below and send it by courier or simply by post.
Send the oil sample to:
- Rodun International BV
- Productieweg 8
- 3481 MH Harmelen
- The Netherlands
How soon can you expect the analysis?
Under normal circumstances, you will receive the results within two to three weeks, possibly with advice for corrective measures. In the case of an urgent analysis, this can be done within 48 hours.
What do the test results actually mean?
Our experience with oil analyses in use enables us to determine the oil property limits. If all test results fall within the 'normal' range, the oil is in good condition, and reported system problems are usually design or operational issues. If one or more properties fall under a 'warning', the necessary corrective measures must be implemented to minimize further change to the oil or the system. Serious deviations require further investigation with more stringent corrective measures or oil replacement to ensure acceptable system operation.
Although the analysis exposes problems and recommends corrective measures, the client can decide for himself which measures he deems necessary and wishes to implement.
Viscosity: Changes in viscosity indicate fouling, thermal stress, and/or oxidation. Viscosity is related to the molecular weight of the oil components. As a rule, contamination by foreign substances in the thermal oil, thermal stress, and oxidation are the causes of an increase or decrease in the oil's viscosity. The operation of the system can be adversely affected by viscosity deviations. If the viscosity is very high, start-up problems may occur, resulting in the burner shutting off. Heat transfer properties may also decrease. At low viscosity, the low-boiling components of the oil can cause cavitation of the pump(s), resulting in a reduced flow.
To remove the low-boiling components, the oil must be routed through the expansion vessel to vent them off.
High viscosity usually requires oil replacement; however, corrections can also be achieved with partial replacement. In all cases, the cause of the change in viscosity values must be investigated. Malfunctioning parts or incorrect oil can cause thermal degradation and oxidation. Repair and a better oil can improve the situation.
Acid number: In general, a high acid number indicates contamination by substances that do not belong in the thermal oil. A high acid number can also result from the absence of 'nitrogen blanketing' on the expansion vessel. If the acid level becomes too high, corrosion occurs and problems can arise. Corrosive materials form sludge and deposits that negatively affect heat transfer. A severe oxidation situation usually requires replacement of the oil.
Moisture: Moisture in the system usually indicates a leak on the process side or that moisture has otherwise entered the system. New systems, flushed with water, open tank valves, etc., can cause moisture in the system. Rust formation, high system pressure, pump cavitation, and vapor lock are usually indications of excessive moisture in the system. If hot oil comes into contact with an accumulation of water, a steam explosion can occur with all the associated consequences. Exceptionally careful start-up of the system with good circulation throughout the entire system is necessary until the water reaches above the boiling point. The heating oil must flow through the expansion tank, where the moisture can be boiled out. In the event of a very large amount of water, the oil must be removed from the system for an external drying process. Leaking system parts must always be repaired promptly, and new oil must prevent water from entering the system.
Note: If drums are stored outdoors, ensure that they are well protected against the effects of rain.
Insoluble dirt: The presence of insoluble dirt generally indicates that the thermal load on the system is too high due to corrosion products and high oxidation. This causes deposits on the heat transfer surface, blockages, and wear on mechanical seals and valves. If this occurs, a bypass filter can often be a solution. If the amounts of dirt are extremely high, consideration should be given to having the fluid filtered externally and thoroughly cleaning the system. Therminol-FF has proven to be very effective in removing deposit products from synthetic and mineral thermal oil systems. In cases of less contamination, a good filter with a fineness between 10 and 25 microns may suffice.
LOW- AND HIGH-BOILING COMPONENTS Low- and high-boiling materials are measured by gas chromatographic analysis and generally show fouling, oxidation, and thermal stress of the oil. This can cause pump cavitation, poor circulation, and reduced heat transfer. This can result in deposits on heat transfer surfaces and insoluble dirt.
To correct this, the layer ducts must be vented and the abnormal thermal stress corrected.
Extreme amounts of low and/or high caulking must be removed externally or the oil must be replaced.
Can I test the oil in my own laboratory?
Rodun's test procedures are based on standard ASTM and/or DIN methods for the analysis of mineral and synthetic chemical liquids. Special analytical tests are not immediately necessary for a rapid visual assessment of the oil's condition. Moisture causes a cloudy liquid or separation between moisture and oil.
The viscosity of new and used oil should be virtually the same. The color of used oil is usually dark brown. A lot of dirt is usually visible at the bottom of a laboratory tube.
In general, it can be stated that thorough laboratory testing is necessary for a proper evaluation of the oil.
MSDS Sheets Rodun International
Would you like to download our MSDS sheets? On this overview page, you will find all MSDS sheets from Rodun International. You can request the data directly in PDF format.
About Rodun International
Thermal oil is our company's specialty. For advice, chemical analyses, and the supply of all synthetic thermal fluids, thermal installations, and systems, you will find the right partner in Rodun International BV. Read more about us on our 'About Rodun International' page. Additionally, follow us on LinkedIn to always stay up to date.