I have water in my thermal system; how do I get it out?
Depending on the pressure and temperature of the thermal fluid, water can expand up to 1,700 times its original volume when converted into steam. It does not matter how it gets into your thermal fluid heater; it is your job to get it out.
Perhaps the first indication is the sudden appearance of hot thermal fluid in the overflow tank (or on the floor of the heating room). Or it could be a drop in pressure in the circulation pump. Whatever it is, water contamination in a working thermal fluid system is difficult to ignore. What makes everyone scratch their heads is that the symptoms of water contamination do not always follow the rules.

They can appear suddenly or over time, at an exhaust temperature of 100℃ or above 260℃. The symptoms can occur when the system is already at operating temperature or is warming up. No matter how or when it starts, it is not good news for anyone involved.
How much water can cause a 'problem'?
Water is almost completely insoluble in thermal fluids, and because it is not mixed, it behaves as water always does: it turns into steam at 100℃.
Depending on the pressure and temperature of the thermal fluid, water can expand up to 1,700 times its original volume when converted into steam. No matter how large the system volume, 200 liters of steam will cause a problem somewhere. Even if the expansion vessel can handle the increase in volume, the resulting cavitation will accelerate pump wear.
Sometimes it is clear that water is going to be a problem. Although every manufacturer warns against it, there are users who insist on using water to test pressure or flush new systems. Drying the system with a nitrogen flush might look good on paper, but the water does not always evaporate within the allowed time.
Sometimes it is not obvious that water will be a problem. For instance, water can enter a system during construction and remain isolated in a cold dead corner for years without causing issues. Ventilated systems in areas with high humidity can become contaminated if the dew point is higher than the temperature of the expansion vessel. Water can enter vessels stored outdoors. Although a visible layer of water in a sample from a low-lying drain is a sign of serious contamination, there are several reasons why the sample might not show any water. Because water droplets do not flow easily along the bottom of the pipe, detecting water in a sample from a single loop (or even two or three) is more a matter of luck than skill. And once the main circulation pump is running, the water will disperse into a “haze” that may not be visible if the liquid has darkened.
Although laboratory tests can detect water down to the level of parts per million, the bottom line is that, no matter how scientific the results are, you will still have to do something about it.